Pramac GRW Series Rental Diesel Generators
The GRW Series is Pramac’s mobile generator range built for hire fleets, construction, events and industry – anywhere a robust set has to be moved, dropped, plugged in and run. Six canopy sizes from 22 to 565 kVA with Stage 3A Yanmar, Perkins and Volvo engines, a long-autonomy metal tank, single-point lifting and a full scope of protection as standard, then configured with the sockets, panels and add-ons your fleet needs.

Designed for mobile and rental work
Long lasting, fast to service and fast to install: the GRW is designed around the three things a hire fleet needs, with safety to ISO 8528 and an IP23 zinc-plated enclosure that shrugs off site life.

Hot parts protected as standard
Metal grids over the engine's hot parts and a glass-fibre insulated exhaust manifold protect operators from contact and keep heat out of the enclosure.

Breaker trips when the power door opens
A switch on the power section door trips the circuit breaker, so cables are connected and disconnected on a dead busbar every time.

Single-point lift, forklift pockets
A single roof lifting eye on a bridge fixed to the base frame, plus forklift pockets and anchor points – fast, safe loading and unloading.

Control panel on the short side
From GRW95P the panel sits on the short side, so two sets stand side by side with all the controls facing the operator – the classic events set-up.

Engine room sealed off from the panel
Total segregation between engine and control panel means no noise breakout when the panel is open while the set is running.

External tank connection built in
A six-way fuel valve is standard, so an external tank can feed the set for long jobs; quick couplings are an option. The metal tank has a filler on each side.

Washable, fireproof soundproofing
Polyurethane foam that can be hosed down, behind metal door grids, keeps noise low and survives years of construction-site dirt. Document holder inside as standard.

Leroy Somer alternator, humid-climate protection
Every GRW uses a Leroy Somer LSA alternator with AREP excitation, D350 digital AVR and Winding Protection System 2 for tropical environments above 95 % humidity.
Six canopy sizes, 22 to 565 kVA
Every GRW Stage 3A is built on one of six canopies – Alfa, Alfa Plus, Beta, Beta Plus, Epsilon and Zeta – with Yanmar, Perkins or Volvo Penta engines and Leroy Somer alternators. Ratings are Emergency Standby Power (ESP) at 50 Hz, 400 V three-phase; expand a card for the models, breaker sizes and run times on the built-in tank.

22–50 kVA ESP · 50 Hz
Engines: Yanmar · Alternator: Leroy Somer · Stage 3A
- Canopy L×W×H
- 2000 × 1200 × 1582 mm
- Super silent L×W×H
- 2000 × 1200 × 2150 mm
- Built-in fuel tank
- 216 L
- Starting battery
- 1 × Optima Red 44 Ah AGM, 12 V
Models in this size (3)
| Model | Engine | Alternator | Breaker | Run time at 75 % / 100 % PRP | |
|---|---|---|---|---|---|
| GRW22Y | Yanmar 4TNV88-BIPGE | Leroy Somer LSA40 M5 | 32 A | 60.2 h / 46.1 h | |
| GRW35Y | Yanmar 4TNV98-ZGPGE | Leroy Somer LSA42.3 S5 | 50 A | 36.3 h / 26.9 h | |
| GRW50Y | Yanmar 4TNV98T-ZGPGE | Leroy Somer LSA42.3 M7 | 63 A | 29.4 h / 21.7 h |

67 kVA ESP · 50 Hz
Engines: Perkins · Alternator: Leroy Somer · Stage 3A
- Canopy L×W×H
- 2400 × 1200 × 1650 mm
- Super silent L×W×H
- 2400 × 1200 × 2230 mm
- Built-in fuel tank
- 280 L
- Starting battery
- 1 × Optima Red 44 Ah AGM, 12 V
Models in this size (1)
| Model | Engine | Alternator | Breaker | Run time at 75 % / 100 % PRP | |
|---|---|---|---|---|---|
| GRW67P | Perkins 1104D-44TG2 | Leroy Somer LSA42.3 L9 | 100 A | 25.9 h / 19.3 h | View product |

95–115 kVA ESP · 50 Hz
Engines: Perkins · Alternator: Leroy Somer · Stage 3A
- Canopy L×W×H
- 3460 × 1200 × 1950 mm
- Super silent L×W×H
- 3460 × 1200 × 2542 mm
- Built-in fuel tank
- 530 L
- Starting battery
- 1 × Optima Red 44 Ah AGM, 12 V
Models in this size (2)
| Model | Engine | Alternator | Breaker | Run time at 75 % / 100 % PRP | |
|---|---|---|---|---|---|
| GRW95P | Perkins 1104D-E44TAG1 | Leroy Somer LSA44.3 S4 | 160 A | 31.3 h / 26.0 h | |
| GRW115P | Perkins 1104D-E44TAG2 | Leroy Somer LSA44.3 S5 | 160 A | 27.0 h / 23.7 h | View product |

165–210 kVA ESP · 50 Hz
Engines: Perkins · Alternator: Leroy Somer · Stage 3A
- Canopy L×W×H
- 3460 × 1200 × 2050 mm
- Super silent L×W×H
- 3460 × 1200 × 2670 mm
- Built-in fuel tank
- 940 L
- Starting battery
- 1 × Optima Red 50 Ah AGM, 12 V
Models in this size (3)
| Model | Engine | Alternator | Breaker | Run time at 75 % / 100 % PRP | |
|---|---|---|---|---|---|
| GRW165P | Perkins 1106D-E70TAG2 | Leroy Somer LSA44.3 L10 | 250 A | 33.5 h / 26.9 h | |
| GRW180P | Perkins 1106D-E70TAG3 | Leroy Somer LSA44.3 VL13 | 250 A | 31.7 h / 25.1 h | |
| GRW210P | Perkins 1106D-E70TAG4 | Leroy Somer LSA44.3 VL14 | 400 A | 27.4 h / 21.8 h |

360–455 kVA ESP · 50 Hz
Engines: Volvo Penta · Alternator: Leroy Somer · Stage 3A
- Canopy L×W×H
- 4165 × 1500 × 2130 mm
- Super silent version
- Not available
- Built-in fuel tank
- 1180 L
- Starting battery
- 2 × Optima Yellow 75 Ah AGM, 12 V
Models in this size (3)
| Model | Engine | Alternator | Breaker | Run time at 75 % / 100 % PRP | |
|---|---|---|---|---|---|
| GRW360V | Volvo TAD1351GE | Leroy Somer LSA46.3 L10 | 630 A | 22.8 h / 17.5 h | |
| GRW405V | Volvo TAD1352GE | Leroy Somer LSA46.3 L11 | 630 A | 20.0 h / 15.7 h | View product |
| GRW455V | Volvo TAD1355GE | Leroy Somer LSA47.3 S5 | 630 A | 17.4 h / 14.0 h |

505–565 kVA ESP · 50 Hz
Engines: Volvo Penta · Alternator: Leroy Somer · Stage 3A
- Canopy L×W×H
- 4630 × 1600 × 2450 mm
- Super silent version
- Not available
- Built-in fuel tank
- 1500 L
- Starting battery
- 2 × Optima Yellow 75 Ah AGM, 12 V
Models in this size (2)
| Model | Engine | Alternator | Breaker | Run time at 75 % / 100 % PRP | |
|---|---|---|---|---|---|
| GRW505V | Volvo TAD1650GE | Leroy Somer LSA47.3 S5 | 800 A | 20.8 h / 15.8 h | |
| GRW565V | Volvo TAD1651GE | Leroy Somer LSA47.3 M7 | 800 A | 18.8 h / 14.7 h | View product |
GRW generators available from Ozwide Power
GRW models configured for the Australian market, in stock or on short lead time. Need a different size, a super silent version or a custom socket kit? Ask us for a quote.
What “GRW67P SS” means
Every GRW model name tells you the standby power, the engine brand and whether it has the super silent enclosure.
- Y – Yanmar
- P – Perkins
- V – Volvo Penta
- SS – Super silent enclosure fitted
- No suffix – standard canopy
Standard scope, ratings and compliance
Every GRW ships with
- Engine–alternator monoblock with Leroy Somer alternator (Winding Protection System 2)
- Metal fuel tank with a filler on each side, six-way fuel valve for an external tank, leak-proof tray with leak sensor
- Optima AGM starting batteries, manual battery switch, manual oil pump, coolant drain facility
- Automatic control panel with 4-pole breaker, adjustable differential protection, external terminal board, hour meter and fuel gauge, door-open breaker trip and breaker status
- Hot parts protection, insulated exhaust manifold, earth rod kit, document holder
- Roof lifting bridge, forklift pockets, canopy bumpers, pull bar (up to Beta Plus), door stops
- Zinc-plated IP23 enclosure with washable UL 94 HF1 soundproofing and a double-primer base frame finish
Power ratings (ISO 8528-1)
ESP – Emergency Standby Power: the maximum power available in a utility outage for up to 200 h per year; average load over 24 h should not exceed 70 % of ESP.
PRP – Prime Power: the maximum power available for unlimited hours per year on a variable load; average load over 24 h should not exceed 70 % of PRP. Run times on this page are quoted at 75 % and 100 % of PRP.
Compliance
- ISO 8528 and CE-marked: Machinery 2006/42/CE, EMC 2014/30/UE, LVD 2014/35/UE, noise 2000/14/EC and emissions 97/68/EC where applicable, RoHS 2011/65
- EN 12100, EN 13857, EN 60204
- 400 V / 230 V three-phase 50 Hz; 60 Hz and other voltages via the voltage selector and dual frequency options
Build your machine block by block
The GRW comes well equipped as standard; the options let you tailor it to the fleet – sockets for the markets you hire into, parallel panels for events, hazardous-area kit for mines and oil and gas.
Every GRW add-on explained
All factory options for the GRW Stage 3A, grouped by block. Pick a block, search, or filter by canopy size – each card shows which sizes it is available for. Availability of some options varies by engine model; Ozwide Power will confirm the exact configuration when quoting.
Control panel options
Automatic or parallel panels, voltage selectors, dual frequency, insulation monitoring, remote monitoring gateways and expansion modules.
17 options

Automatic Control Panel
The standard GRW panel: an automatic mains-failure controller with a 4-pole automatic circuit breaker, all in the segregated control / power / socket cabinet. It runs the set in manual, automatic or remote-start modes and comes with a full scope of protection and instrumentation as standard.
- Controller: Deep Sea DSE7320 MKII (ComAp AMF26-P on some earlier builds up to GRW210P)
- ON/OFF selector switch, analogue fuel level and hour meters, internal voltage-adjust potentiometer
- 5 A battery charger (Deep Sea BC2405)
- Adjustable differential (earth leakage) protection with selector switch (ABB RD3M) – ADI
- 4-pole automatic circuit breaker with thermal and magnetic protection, large busbar with bottom cable entry (ETB), door-open breaker trip (SBT) and breaker status contact (ACB)
- Socket section: two-wire remote start/stop, auxiliary power supply plug, multi-pin connector for a transfer switch (LTS)
- Emergency stop button
Standard on every GRW. Choose ACP or MPP.

Modular Parallel Panel
A synchronising panel with a 4-pole motorised circuit breaker for running several GRW sets in parallel – the classic events and rental set-up where load grows through the day. The controller handles synchronising, load sharing and breaker control automatically.
- Controller: Deep Sea DSE8920 (ComAp InteliGen NTC + InteliVision 5 on some earlier builds up to GRW210P)
- 4-pole motorised circuit breaker with thermal and magnetic protection, busbar with bottom cable entry, door-open breaker trip and breaker status
- Multi-pin connector for the parallel signal cable
- Same standard scope as ACP: selector switch, fuel and hour gauges, 5 A battery charger, adjustable differential protection, emergency stop
Available from GRW67P (Alfa Plus) upwards. Choose ACP or MPP.
Voltage Selector Switch 1 (2 positions)
A two-position voltage selector so one set can serve different supplies: Star for 400/230 V three-phase 50 Hz (480/277 V at 60 Hz) or Parallel Star for 208/120 V three-phase 60 Hz.
- Star: 400/230 V 3-phase 50 Hz – 480/277 V 3-phase 60 Hz
- Parallel star: 208/120 V 3-phase 60 Hz
GRW35Y to GRW210P. Not available on GRW22Y; Epsilon and Zeta on request. With the MPP panel the maximum 60 Hz voltage is 415 V star and the minimum 220 V.
Voltage Selector Switch 2 (3 positions)
A three-position voltage selector covering three-phase 400 V, three-phase 230 V (delta) and 208/120 V at 60 Hz from the same alternator.
- Star: 400/230 V 3-phase 50 Hz – 480/277 V 3-phase 60 Hz
- Parallel star: 208/120 V 60 Hz
- Delta: 230 V 3-phase 50 Hz
GRW35Y to GRW210P. Not available on GRW22Y; Epsilon and Zeta on request. With MPP the 60 Hz limits are 415 V star / 220 V.
Voltage Selector Switch 3 (2 positions)
A two-position selector between 400 V three-phase and 230 V single-phase (double delta), handy for hire sets that alternate between site power and single-phase loads.
- Star: 400/230 V 3-phase 50 Hz – 480/277 V 3-phase 60 Hz
- Double delta: 230 V single-phase 50 Hz
GRW35Y to GRW210P. Not available on GRW22Y; Epsilon and Zeta on request.
Voltage Selector Switch 4 (2 positions)
A two-position selector between 400 V three-phase star and 230 V three-phase delta.
- Star: 400/230 V 3-phase 50 Hz – 480/277 V 3-phase 60 Hz
- Delta: 230 V 3-phase 50 Hz
GRW35Y to GRW210P. Not available on GRW22Y; Epsilon and Zeta on request.
Voltage Selector Switch 5 (2 positions, 50 Hz)
A 50 Hz-only two-position selector between 400 V three-phase star and 230 V three-phase delta.
- Star: 400/230 V 3-phase 50 Hz
- Delta: 230 V 3-phase 50 Hz
GRW35Y to GRW210P; Epsilon and Zeta on request.
Voltage Selector Switch 6 (2 positions, 50 Hz)
A 50 Hz-only two-position selector between 400 V three-phase and 230 V single-phase (double delta).
- Star: 400/230 V 3-phase 50 Hz
- Double delta: 230 V single-phase 50 Hz
GRW35Y to GRW210P; Epsilon and Zeta on request.
Control Section Internal Lighting
A light inside the control section that switches on automatically when the door is opened, so the panel can be read and operated at night or in poorly lit plant areas.
- Automatic switch on the control section door

Engine Analogue Gauges
Traditional analogue gauges on the panel for engine oil pressure and coolant temperature, in addition to the readings on the controller.
- Low oil pressure gauge
- High engine temperature gauge

Dual Frequency Switch (50/60 Hz)
A two-position selector inside the control panel that switches the set between 400 V 50 Hz and 480 V 60 Hz, for fleets that travel between markets or supply 60 Hz equipment.
- 400 V 3-phase 50 Hz ↔ 480 V 3-phase 60 Hz on ACP and MPP panels
- With a socket panel kit fitted the sockets can only be used at 400/230 V
Other frequency/voltage combinations available as special solutions.

Insulation Monitoring Device
An insulation monitor for unearthed (IT) supplies from a mobile generator. It continuously measures the insulation resistance of the system to earth (0 to 300 V) and alarms before a fault becomes dangerous – required by some hire and event customers and for German-market socket kits.
- Bender ISOMETER IR423-D4-2 or DOLD RN 5897/300, depending on socket kit and stock
- Genset wired as an IT system when IMD is ordered
Replaces the standard adjustable differential protection (ADI). Mandatory with socket kit SPKB6.

DSE890 MKII DSEWebNet Gateway 4G + Antenna
A 4G/Ethernet gateway with antenna and built-in GPS that connects the controller to the DSEWebNet cloud, so you can see status, alarms, fuel level and location of every set in the fleet from a phone, tablet or PC and receive email alerts.
- 4G with 2G/3G fallback, any network SIM
- GPS location for asset tracking and geo-fencing
- Connects via USB, RS485, Ethernet or CAN
- Full DSEWebNet access: alarms by email, data logging, reports, iOS/Android app
Not combinable with RGW8, RGW9 or ARM7.

DSE892 SNMP Gateway
A DIN-rail gateway that puts the generator on an SNMP network management system, sending traps and emails on alarms and status changes and answering SNMP GET/SET requests.
- SNMP V2, automatic MIB generation
- Customisable email / SNMP trap messages, SMTP client
- Browser configuration, status LEDs, one gateway for multiple controllers
Not combinable with RGW2, RGW9 or ARM7.

DSE855 USB to Ethernet Communications Device
Converts the controller's USB port to Ethernet with a built-in web server, so a single set can be monitored and controlled over a LAN/WAN or integrated into a building management system via MODBUS TCP.
- In-built web server, browser configuration
- MODBUS TCP, viewable from four locations at once
- DIN rail mount
Not combinable with RGW2, RGW8 or ARM7.

DSE2157 Output (8) Expansion Module
Adds eight configurable relay outputs to the controller for signalling generator status and alarms to external equipment.
- 8 relay contacts with LED indicators: 4 normally open, 4 change-over
- Power on / link lost LED, ID switch
- Terminal strip connections
Not combinable with RGW2, RGW8 or RGW9.
Arrangement for Different Electrical Connection Systems
A busbar arrangement that lets the neutral scheme be changed quickly between TN-S, TN-C, IT and TT, with voltage-presence LEDs and phase-rotation test terminals on the panel door – ideal for hire sets that connect to a different installation every week.
- Busbar arrangement for TN-S, TN-C, IT and TT connection schemes
- 3 LEDs for voltage presence and terminals for phase rotation measurement on the control panel door
- Genset start with breaker open (MPP version only)
Sockets & power locks options
Factory socket outlet kits (European CEE or Australian Clipsal-style) and Power Lock connector boxes on the socket section of the panel. One kit per set.
24 options

Socket Panel Kit A1
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A1 gives you: 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 1 × 230 V CEE 16 A; 1 × 230 V Schuko 16 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 32 A 3P+N+E IP67
- 1 × 400 V CEE 16 A 3P+N+E IP67 – 3P MCBs curve C with common Type A RCD (ABB RD2)
- 1 × 230 V CEE 16 A 2P+E IP67
- 1 × 230 V Schuko 16 A IP67 – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A2
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A2 gives you: 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 1 × 230 V CEE 16 A; 1 × 230 V Schuko 16 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 63 A, 1 × 32 A, 1 × 16 A 3P+N+E IP67 – 3P MCBs curve C with common Type A RCD (ABB RD2)
- 1 × 230 V CEE 16 A 2P+E IP67 and 1 × 230 V Schuko 16 A – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A3
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A3 gives you: 1 × 400 V CEE 32 A; 3 × 230 V CEE 32 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 32 A 3P+N+E IP67 – 3P 32 A MCB curve B
- 3 × 230 V CEE 32 A 2P+E IP67 – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A4
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A4 gives you: 1 × 400 V CEE 63 A; 3 × 230 V CEE 32 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 63 A 3P+N+E IP67 – 3P 63 A MCB curve B
- 3 × 230 V CEE 32 A 2P+E IP67 – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A5
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A5 gives you: 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 2 × 230 V Schuko 16 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 32 A and 1 × 16 A 3P+N+E IP67 – individual 3P MCBs curve B with common Type A RCD (ABB RD2)
- 2 × 230 V Schuko 16 A IP67 – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A6
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A6 gives you: 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 2 × 230 V Schuko 16 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 63 A, 1 × 32 A, 1 × 16 A 3P+N+E IP67 – individual 3P MCBs curve B with common Type A RCD (ABB RD2)
- 2 × 230 V Schuko 16 A IP67 – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A7
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A7 gives you: 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 2 × 230 V Schuko 16 A (MCB only, no RCD). For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 63 A, 1 × 32 A, 1 × 16 A 3P+N+E IP67 – individual 3P MCBs curve B
- 2 × 230 V Schuko 16 A IP67 – individual 2P 16 A MCBs curve B
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A8
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A8 gives you: 1 × 400 V CEE 125 A (unprotected); 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 1 × 230 V CEE 16 A; 1 × 230 V Schuko 16 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 125 A 3P+N+E IP67 with no dedicated protection (under the genset breaker)
- 1 × 400 V CEE 63 A, 1 × 32 A, 1 × 16 A 3P+N+E IP67 – individual 3P MCBs curve B with common Type A RCD (ABB RD2)
- 1 × 230 V CEE 16 A and 1 × 230 V Schuko 16 A – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A9
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A9 gives you: 1 × 400 V CEE 125 A; 1 × 400 V CEE 63 A; 3 × 230 V CEE 32 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 125 A and 1 × 63 A 3P+N+E IP67 – individual 3P MCBs curve B
- 3 × 230 V CEE 32 A 2P+E IP67 – individual 32 A 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A10
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A10 gives you: 1 × 400 V CEE 125 A (unprotected); 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 2 × 230 V Schuko IP68. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 125 A 3P+N+E IP67 with no dedicated protection
- 1 × 400 V CEE 63 A, 1 × 32 A, 1 × 16 A 3P+N+E IP67 – individual 3P MCBs curve B with common Type A RCD (ABB RD2)
- 2 × 230 V Schuko IP68 – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A11
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A11 gives you: 1 × 400 V CEE 125 A (unprotected); 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 230 V CEE 16 A; 2 × 230 V Schuko IP68 – IT earthing system. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 125 A 3P+N+E IP67 with no dedicated protection
- 1 × 400 V CEE 63 A and 1 × 32 A 3P+N+E IP67 – individual 3P MCBs curve B
- 1 × 230 V CEE 16 A 1P+N+E IP67 and 2 × 230 V Schuko IP68 – individual 2P 16 A MCBs curve B
- Wired for an IT earthing system
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A12
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A12 gives you: 2 × 32 A 500 V 4-pin Clipsal-type industrial outlets; 3 × 15 A 250 V single-phase outlets. For 400 V three-phase 50 Hz sets.
- 2 × 32 A 500 V 4-pin IP66 industrial (Clipsal or equivalent) outlets – individual 3P 32 A MCBs curve B with common Type A RCD (ABB RD2)
- 3 × 15 A 250 V single-phase IP66 auto-switched outlets – 2P 30 mA Type A RCBOs
- Australian-style outlet kit
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit A13
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit A13 gives you: 3 × 32 A 500 V 4-pin Clipsal-type industrial outlets; 3 × 15 A 250 V single-phase outlets. For 400 V three-phase 50 Hz sets.
- 3 × 32 A 500 V 4-pin IP66 industrial (Clipsal or equivalent) outlets – individual 3P 32 A MCBs curve B with common Type A RCD (ABB RD2)
- 3 × 15 A 250 V single-phase IP66 auto-switched outlets – 2P 30 mA Type A RCBOs
- Australian-style outlet kit
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit B1
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B1 gives you: 1 × 400 V CEE 125 A; 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 1 × 230 V CEE 16 A; 1 × 230 V Schuko 16 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 125 A, 63 A, 32 A and 16 A 3P+N+E IP67 – individual 3P MCBs with common Type A RCD (ABB RD2)
- 1 × 230 V CEE 16 A 2P+E IP67 and 1 × 230 V Schuko 16 A – individual 2P 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit B2
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B2 gives you: 1 × 400 V CEE 125 A; 1 × 400 V CEE 63 A; 3 × 230 V CEE 32 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 125 A and 1 × 63 A 3P+N+E IP67 – individual 3P MCBs
- 3 × 230 V CEE 32 A 2P+E IP67 – 3 individual 1P+N 16 A 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit B3
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B3 gives you: 1 × 400 V 125 A; 1 × 400 V 63 A; 1 × 400 V 32 A; 1 × 400 V 16 A; 2 × 230 V Schuko 16 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V 125 A, 63 A, 32 A and 16 A 3P+N+E IP67 – individual 3P MCBs with common Type A RCD (ABB RD2)
- 2 × 230 V Schuko 16 A 2P+E IP67 – 2 individual 2P 16 A 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit B5
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B5 gives you: 3 × 32 A 500 V 5-pin 3-pole Clipsal-type industrial outlets; 3 × 15 A 250 V 3-pin single-pole outlets. For 400 V three-phase 50 Hz sets.
- 3 × 32 A 500 V 5-pin 3-pole IP66 industrial (Clipsal or equivalent) outlets – individual 3P 32 A MCBs with common Type A RCD (ABB RD2)
- 3 × 15 A 250 V 3-pin IP66 auto-switched outlets – 3 individual 2P 16 A 30 mA Type A RCBOs
- Australian-style outlet kit
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit B6
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B6 gives you: 1 × 400 V CEE 125 A; 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 1 × 230 V Schuko 16 A IP68 – German Type B RCD spec. For 400 V three-phase 50 Hz sets.
- Each socket with its own Type B 30 mA RCD (63 A socket with 500 mA RCD; 125 A socket under the genset breaker, no RCD)
- Individual 3P MCBs 63 A / 32 A / 16 A curve B; 1 × 2P 16 A 30 mA Type A RCBO for the Schuko
- IT connection – must be ordered with IMD
- Includes 'Stromerzeuger Typ B' sticker above the control panel
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit B7
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B7 gives you: 1 × 400 V CEE 63 A with pilot contact; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 1 × 230 V CEE 16 A; 1 × 230 V Schuko 16 A. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 63 A 3P+N+E IP67 with pilot contact (its MCB opens when the plug is removed)
- 1 × 400 V CEE 32 A and 1 × 16 A 3P+N+E IP67 – individual 4P MCBs with common Type A RCD (ABB RD2)
- 1 × 230 V CEE 16 A and 1 × 230 V Schuko 16 A – 2 individual 2P 16 A 30 mA Type A RCBOs
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit B9
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B9 gives you: 1 × 400 V 125 A; 1 × 400 V 63 A; 1 × 400 V 32 A; 230 V Schuko 16 A – IT system with DOLD isometer. For 400 V three-phase 50 Hz sets.
- 1 × 400 V 125 A, 63 A and 32 A 3P+N+E IP67 – individual 4P MCBs curve C
- 230 V Schuko 16 A 2P+E IP67 – 2P 16 A MCB curve C
- IT system with DOLD RN 5897/300 isometer
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Socket Panel Kit B10
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B10 gives you: 1 × 32 A 500 V 5-pin Clipsal-type outlet with switch; 1 × 400 V CEE 63 A; 1 × 15 A 250 V single-phase outlet with switch. For 400 V three-phase 50 Hz sets.
- 1 × 32 A 500 V 5-pin 3-pole IP66 industrial (Clipsal or equivalent) outlet with individual switch
- 1 × 400 V CEE 63 A 3P+N+E IP67 – individual 3P MCBs with common Type A RCD (ABB RD2)
- 1 × 15 A 250 V 3-pin IP66 auto-switched outlet with individual switch – 2P 16 A 30 mA Type A RCBO
- Australian-style outlet kit
Only one socket panel kit can be fitted per set. Includes an Australian 240 V 15 A in-line plug for the auxiliary (battery charger) supply.

Socket Panel Kit B11
A factory-fitted socket outlet panel on the control panel's socket section, with each outlet individually protected. Kit B11 gives you: 1 × 400 V CEE 125 A; 1 × 400 V CEE 63 A; 1 × 400 V CEE 32 A; 1 × 400 V CEE 16 A; 1 × 250 V Schuko 16 A; IT / TN-S selector switch. For 400 V three-phase 50 Hz sets.
- 1 × 400 V CEE 125 A (no RCD), 63 A (63 A Type B 300 mA RCD), 32 A and 16 A (individual Type B 30 mA RCDs) 3P+N+E IP67 – individual 4P MCBs curve B
- 1 × 250 V Schuko 16 A IP68 – 2P 16 A 30 mA Type A RCBO
- 1 × auxiliary input socket 230 V
- Manual selector switch for IT / TN-S systems with LED indication
Only one socket panel kit can be fitted per set. Every kit includes a CEE 230 V 16 A plug for the auxiliary power supply (battery charger).

Power Lock 400 A
A five-way Power Lock connector box (L1, L2, L3, N, earth) for connecting high-current power cables quickly and safely without opening the busbar compartment – the standard connection for events and temporary power. All ports are keyed and colour-coded so cables cannot be connected to the wrong line.
- 5 × 400 A Power Lock panel connectors (ref. PBX-SL-PS-EU-400): L1, L2, L3, neutral, earth
- 400 A at all voltages, directly protected by the generator's main circuit breaker
- Sequential connection – earth connects first
- Keyed and colour-coded to European 3-phase standards, finger-protected, lockable, IP65 sealed ports
Not combinable with PWL2. Alfa Plus size and above.

Power Lock 660 A
The higher-capacity Power Lock connector box for the largest GRW sets, with five 660 A keyed and colour-coded connectors (L1, L2, L3, N, earth) protected directly by the main circuit breaker.
- 5 × 660 A Power Lock panel connectors (ref. PBX-SL-PS-EU-660): L1, L2, L3, neutral, earth
- 600 A rating at all voltages, sequential earth-first connection
- Keyed, colour-coded, finger-protected, lockable, IP65 sealed ports
Not combinable with PWL1. Epsilon and Zeta sizes only.
Engine options
Cold-start heating, water-separating fuel filtration and heavy-duty dust filtration.
3 options

Pre-Heating System
An engine coolant heater that keeps the engine warm while the set is idle so it starts quickly and takes load promptly in cold weather. Recommended wherever the ambient temperature can drop below 3 °C.
- Yanmar (Alfa): 400 W immersion heater
- Perkins 1104D (Alfa Plus, Beta): 600 W immersion heater
- Perkins 1106D and Volvo (Beta Plus, Epsilon, Zeta): 1500 W external heater with thermostat

Water Separator Filter
A Parker Racor water-separating fuel filter fitted ahead of the engine's own filters. It strips water, dirt, rust, algae and varnish out of the fuel before it reaches the injection system – strongly recommended for hire sets that run on fuel of unknown quality.
- Parker Racor 500FG10 on Yanmar, Perkins 1104D and Volvo engines
- Parker Racor 1000FH10 on Perkins 1106D engines (Beta Plus)
- Protects against dirt, rust, algae, asphaltenes, varnish and water

Heavy-Duty Air Filter
A larger heavy-duty air cleaner that lets the set work in dusty environments – construction sites, mines, quarries – while stretching out the filter service intervals.
- Donaldson D080069 (Alfa), D090073 (Alfa Plus, Beta), D100384 (Beta Plus), D140078 (Zeta)
- Epsilon (Volvo TAD135x) already has a Donaldson D10012x heavy-duty filter as standard
Not combinable with ASV on Volvo engines.
Fuel options
External tank connection and fuel transfer: quick couplings, automatic pump and base frame drain pump.
4 options

Quick Fuel Connectors
Quick-release fuel couplings on the base frame, outside the enclosure, connected to the six-way fuel valve that is standard on every GRW. Hook up an external tank in seconds to extend running time for long events or continuous site work.
- Inlet: male ½" Serie 595 ISO 7241/A; outlet: female ½" Serie 595 ISO 7241/A
- Maximum working pressure 250 bar, flow 43 L/min
- Mounted on the base frame, outside the enclosure
Not combinable with QFC1. Cannot be connected to the AFP pump.

Quick Fit Fuel Connectors inside the canopy
The same quick-release couplings as QFC, but mounted inside the enclosure behind a door so they are protected from damage and tampering.
- Inlet: male ½" Serie 595 ISO 7241/A; outlet: female ½" Serie 595 ISO 7241/A
- Maximum working pressure 250 bar, flow 43 L/min
- Located inside the enclosure, protected by the genset door
Not combinable with QFC.

Automatic Fuel Pump
Two fuel transfer pumps – one electric, controlled automatically, and one manual backup – for filling the generator's built-in tank from an external bulk tank.
- Piusi BP3000 (Perkins sets): 12 V DC, 50 L/min, 300 W, 2900 rpm, 1.5 bar, 30 min duty cycle
- Piusi Panther (Volvo sets): 24/12 V DC, 70/35 L/min, 420/150 W, 3600/1800 rpm, 1.5 bar
- Manual fuel pump included; fuel pipes to the external tank not supplied
Not available on Yanmar (Alfa) sets. Cannot be combined with QFC.

Draining Baseframe Pump
A manual pump for emptying any liquid that has collected in the leak-proof tray of the base frame. A selector switch lets the same pump drain the engine oil, so it doubles as the oil drain pump at service time.
- Manual pump for the base frame leak-proof tray
- Switchable to engine oil draining
Exhaust options
Spark arrestor and air shut-off valve for hazardous areas.
2 options

Exhaust Spark Arrestor
An ATEX-certified spark arrestor on the exhaust outlet that traps hot carbon particles and stops flammable debris being ejected – a mandatory safety item on mine sites, oil and gas, petrochemical, timber and agricultural sites where combustible material, gases or dust may be present.
- Indemar WT2L150SS (Yanmar), WT2L175SS (Perkins), Bastelli PAE171 (Volvo)
- ATEX certified; allows operation in ATEX zones
- Genset noise level may vary by ±4 dB(A) with ESA fitted

Air Shut-Off Valve
An automatic air intake shut-off valve that stops a runaway diesel. If flammable vapour is drawn into the intake the engine can overspeed uncontrollably; the spring-actuated valve blocks the intake completely, starving the engine of both air and the uncontrolled fuel source. Specified for oil and gas, petrochemical and mining sites.
- Chalwyn SVX series valve (SVX501 on Volvo engines)
- Emergency overspeed protection for hazardous areas
Not combinable with HDF on Volvo engines.
Enclosure options
Super silent roof, lighting, bumpers and custom colours.
4 options

Super Silent Enclosure
An additional roof module with internal soundproofing partitions that cuts the noise from the air outlet by up to 5 dB(A) compared with the standard canopy. The choice for events, concerts, sports and any work in residential areas. Models are designated with an SS suffix, e.g. GRW67P SS.
- Noise reduction up to −5 dB(A) versus the standard enclosure
- Overall height: Alfa 2150 mm, Alfa Plus 2230 mm, Beta 2542 mm, Beta Plus 2670 mm (length and width unchanged)
Available on Alfa, Alfa Plus, Beta and Beta Plus sizes (GRW22Y to GRW210P).
Internal Canopy Lighting
Lighting inside the enclosure with a manual ON/OFF switch, so refuelling, checks and servicing can be done safely at night or in low ambient light.
- Internal canopy lighting with manual switch

Baseframe Bumpers
Rubber bumpers on the base frame that reduce the risk of damage during forklift handling and transport – a worthwhile addition for hire fleets that move every week.
- Bumpers at each forklift pocket opening
- Bumpers on each short-side corner
Different Canopy Colour (custom RAL)
Have the canopy finished in a RAL colour of your choice – to match your fleet livery or a customer's branding – with the same durable standard finish.
- Any RAL colour, agreed at order
- Standard finish retained
Lifting & handling options
Sliding skid, site and road trailers.
4 options

Galvanised Sliding Skid
Two galvanised steel slides with the same footprint as the base frame, bolted underneath to raise the set off the ground. They protect the base frame and forklift pocket profiles when the set is dragged across a construction site over debris, rebar and rough ground.
- Two galvanised slides screwed to the standard base frame
- Same shape and footprint as the base frame
- Drawings available for Alfa / Alfa Plus and Beta / Beta Plus sizes
Site Trailer
A site (non-road-registered) trailer for moving the generator around a site or event ground. Specified and quoted case by case to suit the size of set and your requirements.
- Quoted per project by Pramac's special solutions team
Ask Ozwide Power for a trailer quote with your generator.
Road Trailer – fixed drawbar
A road-going trailer with a fixed drawbar, specified and quoted case by case for the size of set.
- Quoted per project by Pramac's special solutions team
Ask Ozwide Power for a trailer quote with your generator.
Road Trailer – height-adjustable drawbar
A road-going trailer with a height-adjustable drawbar to suit different tow vehicles, specified and quoted case by case for the size of set.
- Quoted per project by Pramac's special solutions team
Ask Ozwide Power for a trailer quote with your generator.
Battery options
Battery isolation.
1 options

Dual Battery Switch
A two-pole battery isolator that disconnects both battery poles for complete isolation of the starting battery during transport, storage and maintenance.
- Two-pole battery switch for complete battery disconnection
Option currently under development – availability to be confirmed at order.
Other options
Australian-market configuration.
1 options

Special Version for Australian Market
Configures the set for Australian standards: cables colour-marked to AS/NZS 3000, a MEN link between the main earth bar and the main neutral bar, and a bracket provision on the enclosure for a fire extinguisher.
- Cable colour marking to AS/NZS 3000
- MEN link between main earth terminal bar and main neutral conductor bar
- Enclosure provision for a fire extinguisher bracket (extinguisher supplied and fitted locally)
Ozwide Power specifies JAUS on GRW sets supplied for Australia.
Configure your GRW with Ozwide Power
As a Pramac Authorised Dealer we’ll spec the right size, socket kit, panel and add-ons for your fleet or project, and deliver Australia-wide. Call 08 6385 1104 or request a quote and we’ll come back with a configured proposal.