Description
Pramac GDW65P – 66.3 kVA Three Phase Diesel Generator, 500 L Tank
Perkins power. Mecc Alte output. Canopy quiet.
The GDW65P 500L tank generator is the GDW65P/FNE supplied on the MFT-L 500 litre sub-base fuel tank, delivering 66.3 kVA / 53 kW emergency standby and 60.1 kVA / 48.1 kW prime power from a Perkins 1103A-33TG2, a three cylinder, 3.3 litre, turbocharged, water-cooled engine running at 1500 RPM with mechanical governor. Output is delivered through a brushless Mecc Alte ECP32-2M4 C alternator in series star at 400/230 V, 50 Hz, three phase, 0.8 power factor, with class H insulation, IP23 protection, 89.4% efficiency at full load and voltage regulation held inside 1%. Nominal current is 87 A behind a 100 A circuit breaker.
The canopy version is a weatherproof galvanised sheet metal enclosure with residential silencer and high quality soundproofing, giving 64 dB(A) at 7 metres and a guaranteed sound power level of 93 dB(A). Large lockable lateral doors open the unit up for service, and the welded steel baseframe carries anti-vibration mountings, screwed support legs and a crane lifting hole. The canopy measures 2200 x 1020 x 1292 mm and weighs 1037 kg. An extra silent enclosure is available at 60 dB(A) at 7 metres.
On the 500 litre MFT-L sub-base tank the set runs 48.40 hours at 75% prime power. The sub-base tank adds 354 mm to the height and 216 kg to the weight of the canopy, so the unit as supplied is 2200 x 1020 x 1646 mm and 1253 kg (derived from the canopy figures plus the tank figures on the data sheet).
GDW65P at a glance
- 66.3 kVA / 53 kW emergency standby, 60.1 kVA / 48.1 kW prime power
- Perkins 1103A-33TG2, 3 cylinder in line, 3300 cm³, turbocharged, water cooled, 1500 RPM
- Mecc Alte ECP32-2M4 C brushless alternator, 89.4% efficiency at full load, 4 pole, class H, IP23
- 400/230 V, 50 Hz, three phase, 0.8 power factor
- Nominal current 87 A, 100 A circuit breaker
- Fuel consumption 10.33 L/h at 75% PRP, 13.90 L/h at 100% PRP
- Fuel tank options: 8PFT 80 L, MFT-XS 65 L, MFT-S 120 L, MFT-M 245 L, MFT-L 500 L
- Runtime at 75% PRP: 7.74 h (8PFT), 6.29 h (MFT-XS), 11.62 h (MFT-S), 23.72 h (MFT-M), 48.40 h (MFT-L)
- Noise: 64 dB(A) @ 7 m, 76 dB(A) @ 1 m, guaranteed LWA 93 dB(A)
- Control panel: MRS manual remote start or ACP automatic mains failure, specify when ordering
- 12 V electric start, 8.3 L oil capacity, 10.2 L coolant capacity, 80 Ah battery
Optional equipment includes pre-heating (PHS), heavy-duty air filter (HDF), water separator filter (WSP), exhaust spark arrestor (ESA), hot parts protection (HPP), alternator winding total protection (WTP), anti-condensation heater (ACH), a galvanised skid base with fork lift points (GSB), an external terminal board (ETB) and differential protection (ADI). Open and extra silent enclosure versions are available on request.
Compliant with ISO 8528 and EC mark directives, with G2 class load acceptance to ISO 8528-5.
| POWER RATING | ||
| EMERGENCY STANDBY POWER ESP | kVA | 66.3 |
| EMERGENCY STANDBY POWER ESP | kW | 53 |
| PRIME POWER PRP | kVA | 60.1 |
| PRIME POWER PRP | kW | 48.1 |
| VOLTAGE | V | 400/230 |
| FREQUENCY | Hz | 50 |
| POWER FACTOR | cos φ | 0.8 |
| PHASES | 3 | |
| FUEL | Diesel | |
| ENGINE SPECIFICATIONS | ||
| EXHAUST EMISSION LEVEL | Non Emission Certified | |
| ENGINE BRAND | Perkins | |
| MODEL | 1103A-33TG2 | |
| NR. OF CYLINDERS AND DISPOSITION | 3 in line | |
| DISPLACEMENT | cm³ | 3300 |
| ASPIRATION | Turbocharged | |
| ENGINE COOLING SYSTEM | Water | |
| SPEED GOVERNOR | Mechanical | |
| OPERATION SPEED NOMINAL | RPM | 1500 |
| OIL CAPACITY | l | 8.3 |
| COOLANT CAPACITY | l | 10.2 |
| STARTING SYSTEM | Electric | |
| ELECTRIC CIRCUIT | V | 12 |
| FUEL | Diesel | |
| ALTERNATOR SPECIFICATIONS | ||
| ALTERNATOR BRAND | Mecc Alte | |
| MODEL | ECP32-2M4 C | |
| TYPE | Brushless | |
| WINDING CONNECTION | Series star | |
| POLES | 4 | |
| CLASS | H | |
| IP PROTECTION | 23 | |
| VOLTAGE TOLERANCE | % | 1 |
| EFFICIENCY @ 100% LOAD | % | 89.4 |
| FUEL TANK AND AUTONOMY | ||
| FUEL CONSUMPTION @ 75% PRP | l/h | 10.33 |
| FUEL CONSUMPTION @ 100% PRP | l/h | 13.90 |
| 8PFT FUEL TANK CAPACITY (INTERNAL) | l | 80 |
| 8PFT RUNNING TIME @ 75% PRP | h | 7.74 |
| MFT-XS FUEL TANK CAPACITY (INTERNAL) | l | 65 |
| MFT-XS RUNNING TIME @ 75% PRP | h | 6.29 |
| MFT-S FUEL TANK CAPACITY (SUB-BASE) | l | 120 |
| MFT-S RUNNING TIME @ 75% PRP | h | 11.62 |
| MFT-M FUEL TANK CAPACITY (SUB-BASE) | l | 245 |
| MFT-M RUNNING TIME @ 75% PRP | h | 23.72 |
| MFT-L FUEL TANK CAPACITY (SUB-BASE) | l | 500 |
| MFT-L RUNNING TIME @ 75% PRP | h | 48.40 |
| DIMENSIONS, WEIGHT AND NOISE | ||
| OPEN DIMENSIONS (L X W X H) | mm | 1875 x 1000 x 1203 |
| OPEN WEIGHT | kg | 823 |
| CANOPY DIMENSIONS (L X W X H) | mm | 2200 x 1020 x 1292 |
| CANOPY WEIGHT | kg | 1037 |
| CANOPY GUARANTEED NOISE LEVEL LWA | dB(A) | 93 |
| CANOPY NOISE PRESSURE LEVEL @ 1 M | dB(A) | 76 |
| CANOPY NOISE PRESSURE LEVEL @ 7 M | dB(A) | 64 |
| CANOPY EXTRA SILENT DIMENSIONS (L X W X H) | mm | 2200 x 1020 x 1883 |
| CANOPY EXTRA SILENT WEIGHT | kg | 1206 |
| CANOPY EXTRA SILENT GUARANTEED NOISE LEVEL LWA | dB(A) | 89 |
| CANOPY EXTRA SILENT NOISE PRESSURE LEVEL @ 1 M | dB(A) | 72 |
| CANOPY EXTRA SILENT NOISE PRESSURE LEVEL @ 7 M | dB(A) | 60 |
GDW Series – Stationary Generators
Modular. Scalable. Built to Last.
The GDW Series represents a high-performance range of stationary diesel generators engineered for reliable, long-duration power supply. Covering 10 to 820 kVA, the series is suited to both standby and continuous applications across commercial, industrial, and mission-critical environments. Its modular design allows configurations to be tailored to specific operational requirements, site conditions, and regulatory standards.
Available in Open, Silent, and Extra Silent versions, the GDW Series supports multiple enclosure types, fuel tank sizes, and advanced control options. Whether the requirement is low-noise operation in urban areas or robust infrastructure for remote industrial sites, each unit is built to deliver long-term durability and dependable performance.
Key Features
- Power range: 10 to 820 kVA
- Frequency options: 50/60 Hz, single or three phase
- Enclosure choices: Open, Silent, Extra Silent
- Scalable fuel tank autonomy: 8, 12, 24, 48+ hours
- Control systems: Manual, Automatic, Parallel, with remote capability
- High safety standards: weather-resistant enclosures, lockable panels, segregated control/power sections
- Transport-ready design: fork pockets, lifting points, compact footprint
- Easy servicing with wide access doors and quick battery access
- Built using durable, recyclable materials
These generators are engineered for industries where uninterrupted power is essential, such as hospitals, data centres, mining operations, wastewater facilities, and heavy commercial sites.
Frequently Asked Questions
Which applications is the GDW Series suitable for?
The GDW Series is designed for emergency standby and continuous power applications: hospitals, data centres, retail, oil and gas, mining, power plant production, water treatment, among others.
Which versions of GDW are available?
The GDW Series is available in three versions: Open, Silenced Enclosure and Extra Silenced Enclosure. Each version has a sturdy design with robust structure and enclosure, large control and power sections, and a modular core configuration compatible with a wide list of modules to cover all stationary application needs.
How long will the GDW65P run on a full tank?
At 75% prime power it runs 7.74 hours on the 80 litre 8PFT internal tank, 6.29 hours on the 65 litre MFT-XS internal tank, 11.62 hours on the 120 litre MFT-S sub-base tank, 23.72 hours on the 245 litre MFT-M sub-base tank and 48.40 hours on the 500 litre MFT-L sub-base tank. Fuel consumption is 10.33 litres per hour at 75% load and 13.90 litres per hour at 100% load.
Product Video