Description
Pramac GSW22P – 22 kVA Three Phase Diesel Generator
Perkins power. Mecc Alte output. 65 dB(A) at 7 metres.
The GSW22P three phase diesel generator delivers 22 kVA / 17.6 kW emergency standby and 20.01 kVA / 16.01 kW prime power from a Perkins 404A-22G1, a four cylinder, 2.2 litre, naturally aspirated, water-cooled engine with mechanical governor and 12 V electric start. Output is delivered through a brushless Mecc Alte ECP28-M4 C alternator at 400 V, 50 Hz, three phase, 0.8 power factor, with class H insulation, IP23 protection, digital DSR voltage regulation held inside 1% and 88.2% efficiency at 75% load. Maximum current is 31.76 A behind a 32 A circuit breaker.
The soundproof canopy keeps noise to 65 dB(A) at 7 metres with a guaranteed sound power level of 94 dB(A). The unit measures 1800 x 850 x 1260 mm and weighs 706 kg dry.
The 68 litre plastic fuel tank with rotary fuel pump runs 17.22 hours at 75% prime power and 12.88 hours at full load. Control panel options are the MCP manual panel with analogue instrumentation, the MPF manual panel full option with enhanced instrumentation, or the ACP automatic control panel with digital control unit. The standard socket kit on the MCP panel is one 3P+N+T CEE 400 V 32 A, one 3P+N+T CEE 400 V 16 A, two 2P+T CEE 230 V 16 A and one 230 V 16 A SCHUKO outlet; the MPF panel carries the same 400 V and 230 V CEE outlets in IP67 with an IP68 SCHUKO.
GSW22P at a glance
- 22 kVA / 17.6 kW emergency standby, 20.01 kVA / 16.01 kW prime power
- Perkins 404A-22G1, 4 cylinder in line, 2216 cm³, naturally aspirated, water cooled, mechanical governor
- Mecc Alte ECP28-M4 C brushless alternator, 4 pole, class H, IP23, DSR digital regulation, 88.2% efficiency at 75% load
- 400 V, 50 Hz, three phase, 0.8 power factor
- Maximum current 31.76 A, 32 A circuit breaker
- 68 L plastic fuel tank with rotary fuel pump
- Fuel consumption 3.95 L/h at 75% PRP, 5.28 L/h at 100% PRP
- Runtime 17.22 h at 75% PRP, 12.88 h at 100% PRP
- Noise: 65 dB(A) @ 7 m, guaranteed LWA 94 dB(A)
- Control panel: MCP manual, MPF manual full option or ACP automatic, specify when ordering
- 12 V electric start, 80 Ah battery, 10.6 L oil capacity, 7 L coolant capacity
- Dimensions 1800 x 850 x 1260 mm, dry weight 706 kg
Optional supplements include remote control (RCG) and remote signal (TLP) modules, adjustable differential protection (ADI), four pole circuit breaker (TIF), external terminal board (ETB), premium kit with leak proof tray, sensor and pump (KPR), rental kit (KRT), load transfer switch (LTS) and socket kit B (SKB).
Ratings to ISO 8528/1, ISO 3046/1:1986 and BS 5514/1; alternator to CEI 2-3, IEC 34-1, EN 60034-1, VDE 0530, BS 4999-5000 and CAN/CSA-C22.2.
| POWER RATING | ||
| EMERGENCY STANDBY POWER ESP | kVA | 22 |
| EMERGENCY STANDBY POWER ESP | kW | 17.6 |
| PRIME POWER PRP | kVA | 20.01 |
| PRIME POWER PRP | kW | 16.01 |
| MAXIMUM CURRENT | A | 31.76 |
| CIRCUIT BREAKER | A | 32 |
| VOLTAGE | V | 400 |
| FREQUENCY | Hz | 50 |
| POWER FACTOR | cos φ | 0.8 |
| PHASES | 3 | |
| FUEL | Diesel | |
| ENGINE SPECIFICATIONS | ||
| EXHAUST EMISSION LEVEL | Non Emission Certified | |
| ENGINE BRAND | Perkins | |
| MODEL | 404A-22G1 | |
| NR. OF CYLINDERS AND DISPOSITION | 4 in line | |
| DISPLACEMENT | cm³ | 2216 |
| ASPIRATION | Natural | |
| ENGINE COOLING SYSTEM | Water | |
| SPEED GOVERNOR | Mechanical | |
| OIL CAPACITY | l | 10.6 |
| COOLANT CAPACITY | l | 7 |
| STARTING SYSTEM | Electric | |
| ELECTRIC CIRCUIT | V | 12 |
| FUEL | Diesel | |
| ALTERNATOR SPECIFICATIONS | ||
| ALTERNATOR BRAND | Mecc Alte | |
| MODEL | ECP28-M4 C | |
| TYPE | Brushless | |
| POLES | 4 | |
| CLASS | H | |
| IP PROTECTION | 23 | |
| VOLTAGE REGULATION SYSTEM | DSR digital | |
| VOLTAGE TOLERANCE | % | 1 |
| EFFICIENCY @ 75% LOAD | % | 88.2 |
| FUEL TANK AND AUTONOMY | ||
| FUEL TANK CAPACITY (PLASTIC) | l | 68 |
| FUEL CONSUMPTION @ 75% PRP | l/h | 3.95 |
| RUNNING TIME @ 75% PRP | h | 17.22 |
| FUEL CONSUMPTION @ 100% PRP | l/h | 5.28 |
| RUNNING TIME @ 100% PRP | h | 12.88 |
| DIMENSIONS, WEIGHT AND NOISE | ||
| CANOPY DIMENSIONS (L X W X H) | mm | 1800 x 850 x 1260 |
| CANOPY WEIGHT | kg | 706 |
| CANOPY GUARANTEED NOISE LEVEL LWA | dB(A) | 94 |
| CANOPY NOISE PRESSURE LEVEL @ 7 M | dB(A) | 65 |
GSW Series – Stationary Diesel Generators
Reliable. Silent. Ready for Any Demand.
The GSW Series is a proven line of stationary diesel generators engineered for dependable long-term performance across industrial, commercial and critical-power environments. Designed with durability, acoustic comfort and operational efficiency in mind, each generator integrates robust mechanical components with advanced control systems to deliver stable and reliable power, day after day, in all conditions.
Key Features
- Perkins engines paired with Mecc Alte or Leroy Somer brushless alternators
- Sound-attenuated, weatherproof canopies built from modular zinced steel panels with rock wool soundproofing
- Integrated plastic fuel tank with minimum level sensor and extended tank options
- MCP manual, MPF manual full option or ACP automatic control panels
- Lockable access doors, emergency stop and single detachable lifting eye
- Ratings to ISO 8528 with engine performance to ISO 3046/1 and BS 5514/1
Optional equipment includes remote control (RCG) and remote signal (TLP) supplements, adjustable differential protection (ADI), four pole circuit breaker (TIF), external terminal board (ETB), premium kit with leak proof tray and oil drain pump (KPR), rental kit (KRT), coolant pre-heating (PHS) and a load transfer switch (LTS).
Frequently Asked Questions
Which control panels are available on the GSW Series?
The MCP manual control panel with analogue instrumentation, the MPF manual control panel full option with enhanced instrumentation and IP67 sockets, or the ACP automatic control panel with a digital control unit, automatic mains failure operation, automatic battery charger and RS232 communication.
Can the GSW be used for automatic standby?
Yes. With the ACP automatic control panel and the optional LTS load transfer switch the set will start on mains failure, take the load and shut down again when the mains returns.
How long will the GSW22P run on a full tank?
The 68 litre tank gives 17.22 hours at 75% prime power or 12.88 hours at full load, using 3.95 and 5.28 litres per hour respectively.
Is an automatic transfer switch (ATS) included?
No. An automatic transfer switch is not included unless it is listed in the product description above. Ozwide Power can supply a correctly rated ATS with the generator, so ask for a package price when you enquire.